Load vacuum switch FZN25-12FZRN25-12D

Load vacuum switch, Vacuum switch, vacuum breaker

Products details:

General

FZN25-12/FZ(R)N25-12D/T indoor high-voltage AC vacuum load switch and FZRN25-12D/T25-31.5 indoor high-voltage AC vacuum load switch-breaker combination electrical appliances are three-phase AC 50H, 12KV power distribution systems The control and protection device of the product is oil-free, non-toxic, non-flammable and explosion-free. It is widely used in industrial and mining enterprises and urban building power distribution stations. The latter has more reliable protection for electrical equipment such as transformers than circuit breakers. Especially suitable In the ring network, dual auxiliary injection power supply units and box-type substations.


FZN25-12D/T630-20 indoor high-voltage AC vacuum load switch hereinafter referred to as load switch is an indoor device with three-phase AC 50H and rated voltage 12KV, suitable for industrial and mining enterprise power distribution stations and substations, as the protection of electrical facilities And control, used to switch load current, closed loop current, no-load transformer and cable charging current. It has a grounding switch capable of closing short-circuit current. The operating mechanism can be manual or electric, which is convenient to realize the three remote control requirements of the power system.

The FZRN25-12D/T25-315 indoor high-voltage AC vacuum load switch-fuse combination appliance (hereinafter referred to as the combination appliance) is an indoor device with a three-phase AC 50 and a rated voltage of 12V. It is suitable for industrial and mining enterprise power distribution stations and substations, etc. In occasions, it also has a grounding switch capable of closing short-circuit current for load control and short-circuit protection. The operating mechanism can be manual or electric, which is convenient to realize the three remote control requirements of the power system.

The main technical parameters

 
      
Serial numberItemUnitParameter
FZN25-12D/T630/20FZRN25-12D/T200/31.5
1Rated voltagekV1
2
2Rated currentA630200
3Rated frequencyHz50
4Rated absolute1 minute Power frequency withstand voltagekVInterrupter fracture 30; to ground, phase 42; isolation fracture 48
Lightning impulse withstand voltage (peak value)KV75 to ground and between phases; isolation port 85
5Current before rated short circuitkA20 
6Rated short-circuit durationS4 
7Rated peak withstand currentkA50 
8Rated effective load breaking currentA630 
9Rated closed loop breaking currentA630 
10Rated cable charging breaking currentA10 
11Rated breaking no-load transformer capacitykVA1600
12Rated short-circuit breaking currentkA31.5
13Rated transfer currentA 200
14Fuse model  SDLAJ-12 SFLAJ-12
15Impactor output energyJ 1+0.5
16Rated short-circuit making currentkA5080(Expected value)
17Grounding switch rated short-time withstand currentkA20
18Grounding switch rated short-circuit durationS2
19Grounding switch rated peak withstand currentkA50
20Auxiliary circuit rated voltageV220 / 110
21Mechanical lifeTime10000

Overall dimension

The main technical parameters