FZN25-12

Indoor Medium Voltage Vacuum Load Break Switch

12kV 630A

FZN25-12

Description

FZN25-12D/T630-20 Indoor AC medium voltage vacuum load break switch is three-phase AC 50/60 Hz, rated voltage 12kV indoor installation, which is suitable for using in industrial and mining situation and so on enterprise substation and transformer and cable charging current. It had manual and motor operating mechanism that is advantageous to realize remote control. FZRN25-12D/T[]-31.5 indoor AC medium voltage vacuum load break switch with fuse combination, The versions combined with HRC fuses are particularly suitable for the protection of distribution transformers up to 1250 kVA, to break fault current and over load current.

Specifications

 Technical Information

Technical Specification

 

 

Rated voltage

kV

12

Rated current

A

630

Rated power frequency

Hz

50/60

Short circuit making capacity

kA Peak.

50

Peak withstand current

kA Peak.

50

Short time current

kA eff.

 

1Sec.

 

25

3Sec.

 

20

Max. breaking capacity in co-operation with fuses IEC 62271-105(IEC 420 1990-11)

A

2000

Max. fuse current(XRNT Fuse)

A

200

Power frequency withstand voltage 50Hz 1 min,:

 

 

– To earth and between poles

kV

42

– Across isolating distance

kV

48

Impulse withstand voltage 1.2/50μ s:

 

 

– To earth and between poles

kV

75

– Across isolating distance

kV

85

Mechanism Endurance

 

 

-Vauum interrupter

cycles

10000

-Main switch and Earth Switch

cycles

2000

Drawing

Download