FKN12 Series

Indoor High Voltage Load Break Switch

12kV 630A

FKN12

Description

The switch disconnectors series FKN12 are increasingly adopted in MV installations, owing to their superior interrupting features and to their capability to withstand the short-circuit currents which occur mainly as consequences of faults in distribution networks. The versions combined with HRC fuses are particularly suitable for the protection of distribution transformers up to 1250 kVA The use of FKN12, designed for installation in compartmented switchboards have the following advantages: -Full segregation between the busbar compartment and the cable compartment, with switch disconnector in both “closed” and “open” position. -The moving contact, of the sliding vertical type, can be easily checked and cleaned with live bus-bars and earthing switch (ES) closed. -No adjustment is needed in the tripping mechanism of the switch fuse combination and of the ES: they are built together in a single unit, which is adjusted and checked during assembly in the factory, before the final test.

Specifications

Technical Information

Technical Specification

 

 

Rated voltage

kV

12

Rated current

A

630

Rated power frequency

Hz

50/60

Short circuit making capacity

kA Peak.

67

Peak withstand current

kA Peak.

82

Short time current

kA eff.

 

1Sec.

 

31.5

2Sec.

 

25

3Sec.

 

20

Max. breaking capacity in co-operation with fuses IEC 62271-105(IEC 420 1990-11)

A

1600

Max. fuse current(XRNT Fuse)

A

125

Power frequency withstand voltage 50Hz 1 min,:

 

 

– To earth and between poles

kV

42

-Across isolating distance

kV

45

Impulse withstand voltage 1.2/50μ s:

 

 

– To earth and between poles

kV

75

– Across isolating distance

kV

85

Mechanism Endurance

cycles

2000

Drawing