ZW32Q-12
ZW32Q-12 type dual power supply automatic conversion high-voltage vacuum circuit breaker outside the city
12kV
630A 1250A
Description
ZW□ Q-12 series outdoor dual power supply automatic switching vacuum circuit breaker, when the common power supply fails, the switching device can complete the automatic switching with the equipment power supply to ensure reliability and safety. It can also select and switch between two power sources according to the needs of the load. The product has overload and short-circuit protection functions and an interlock design. It is especially suitable for important places where power interruption is not allowed. As an important electrical control device to ensure continuous power supply, it is a self-injection and self-recovery dual-circuit power automatic switching device matched with a high-voltage vacuum circuit breaker. It is a new generation of dual power supply automatic switching products with novel design, perfect performance, safety and reliability, high degree of automation and wide application range. The products are widely used in 10KV power distribution lines in oil fields and mines, and 10KV lines in industrial and mining industries.
Specifications
Main parameters of circuit breaker
No. | Item | Unit | Data | ||
1 | Rated voltage | kV | 12 | ||
2 | Rated current | A | 630 | 1250 | |
3 | Rated insulation level | Power frequency withstand voltage (1min) | kV | 42 | |
Lightning impulse withstand voltage (peak value) | kV | 75 | |||
4 | Secondary circuit 1min power frequency withstand voltage | kV | 2 | ||
5 | Rated short-circuit breaking current | kA | 16/20 | 20 | |
6 | Rated short-circuit making current (peak value) | kA | 40/50 | 50 | |
7 | Rated peak withstand current | kA | 40/50 | 50 | |
8 | 4S rated short-time withstand current | kA | 16/20 | 20 | |
9 | Nominal operating sequence | O-0.3s-CO-180s-CO | |||
10 | Rated short-circuit current breaking times | times | 30 | ||
11 | Mechanical life | times | 10000 | ||
12 | Operating voltage and auxiliary circuit rated voltage | V | DC、AC110,200、AC48,24 | ||
13 | Allowable wear thickness of moving and static contacts | mm | 3 | ||
14 | Rated current of overcurrent release | A | 5 |
The main technical parameters of the controller
No. | Item | Unit | Data |
1 | Rated voltage | V | AC220 |
2 | Rated frequency | Hz | 50 |
3 | Waveform distortion | <10% | |
4 | Overcurrent adjustable range | A | 4-7 |
5 | Over speed adjustable range | A | 4-16 |