FN16A Series

Indoor Vacuum load Break switch

12kV 24kV 40.5k

fn16

Description

FN16A Series

FN16A indoor AC M.V Vacuum load break switch are developed by our company The products follow GB3804-90《3-62kV AC H.V load switch》and IEC62271《 AC H.V. indoor load break switch-fuse combinations》 (2002 edition). These switches are small volume, beautiful appearances, flexible installation, and easy operation. This switch applied for the 50/60Hz, 6-24kV Power distribution system. It can break on load current, and fuse combination can break the over load current and short circuit current. Load break switch with-fuse combinations are also used for protecting over load of transformer and avoiding short-circuit current.

Specifications

FN16A Series

 

Technical Specification

   

Rated voltage

kV

12

24

Rated current

A

630

630

Rated power frequency

Hz

50/60

50/60

Short circuit making capacity

kA Peak.

50

31.5

Peak withstand current

kA Peak.

50

50

Short time current

kA eff.

  

1Sec.

 

25

 

3Sec.

 

20

20

Max. breaking capacity in co-operation with fuses IEC 62271-105(IEC 420 1990-11)

A

2000

2000

Max. fuse current(XRNT Fuse)

A

200

200

Power frequency withstand voltage 50Hz 1 min,:

   

– To earth and between poles

kV

42

65

– Across isolating distance

kV

48

79

Impulse withstand voltage 1.2/50μ s:

   

– To earth and between poles

kV

75

125

– Across isolating distance

kV

85

145

Mechanism Endurance

   

-Vauum interrupter

cycles

10000

10000

-Main switch and Earth Switch

cycles

2000

2000

 

Drawing

FN16A Series

Download