ANSI 57-2

Porcelain Line Post Insulator

Porcelain Line Post Insulator: ANSI 57-2

Description

Porcelain insulator includes Suspension type, Pin type, Spool type, Strain/Guy type, Line Post type and Station Post type, which meet IEC, ANSI, AS, BS, etc. standards.

Line Post Insulator can be used to replace the Pin Type Insulators in a position to reinforce the operational voltage and mechanical strength of the Insulator. It is used for insulating and supporting conductors. There are two versions, tie top conductor binding and clamp top with vertical or horizontal mounting.
Line Post Insulator includes:
1. Line Post Insulator to meet ANSI C29.7
ANSI 57-1, 57-2, 57-3, 57-4, 57-5
2. Vertical Mounting Line Post Insulators to meet ANSI C29.7
ANSI 57-11, 57-12, 57-13, 57-14, 57-15

Specifications

Fig. No.11111
ANSI Class57-1L
57-1S
57-2L
57-2S
57-3L
57-3S
57-4L
57-4S
57-5L
57-5S
Creepage distance (mm)35655973710151145
Dry arcing distance (mm)165241311368438
Cantilever strength (kN)12.512.512.512.512.5
Low frequency flashover (kV)Dry (kV)80110125150175
Wet(kV)6085100125150
Critical impulse flashoverPositive (kV)130180210255290
Negative (kV)155205260340380
Radio influence
voltage
Test voltage to ground (kV)1522304444
Maximum RIV at 1000kHz (uV)100100200200200
Net weight, Each, Approx (kg)6.81011.815.918.6
Nos. in standard package (Nos.)63322

Drawing

Porcelain Insulator: ANSI 57-2 - Drawing