CA-ZN85-33
33kV Indoor Vacuum Circuit Breaker
33kV 40.5kV
1250A 1600A 2000A 2500A
Description
General
CA-ZN85-33 series vacuum circuit breaker is a new type of three-phase 50Hz according to the unique design concept and combined with the market demand and development, the rated voltage of indoor switchgear 33-40.5kV, it can be provided to industrial and mining enterprises, powerplant and substation as the control and protection of electrical equipment,and is suitable for frequent operation.
Advantages
ZN85-33 Vacuum circuit-breakers have particular advantages for use in networks where there is a high switching frequency in the working current range and/ or where a certain number of short- circuit breaking operations are expected. CA-ZN85-40.5 vacuum circuit- breakers are suitable for auto reclosing and have exceptionally high operating reliability and long life. The circuit- breakers are notable for their compact design, small dimensions together with high capacity. The operating mechanisms have a low maintenance requirement and the interrupters are maintenance- free throughout their service lives. They are well suited to all load breaking operations which occur in practice, and in particular:
◇ Short-circuit currents;
◇ Overhead lines under load and, no-load conditions;
◇ Cables under load and no-load conditions;
◇ Transformers under load and no-load conditions;
◇ Generators under load and no-load conditions;
◇ Ripple control system;
◇ Capacitor banks(also parallel switching) and Motors with starting currents above 600A;
Fields of application
◇ Cable control and protection
◇ Overhead control and protection
◇ Transformers and distribution substations
◇ Motor and transformer control and protection
◇ Generator control and protection
◇ Capacitor bank control and protection
Environmental Conditions
Ambient Conditions:
1.Ambient air temperature : Upper limit: +40°C, lower limit: -25°C.
2.Altitude : 1000m above sea level and below.
3.Relative humidity : Monthly average not greater than 90%, daily average not greater than 95%.
4.The surrounding air should be free from obvious pollution such as corrosive or combustible gases and water vapour bodies.
5.No regular strenuous movement.
6.Fouling resistance class: Class II.
Specifications
Technical Parameters
Item | Unit | Parameter | ||
Rated voltage | kV | 33 | ||
Rated current | A | 1250 | 1600 | 2000, 2500 |
Rated short-circuit breaking current | kA | 25/31.5 | 25 | 31.5 |
Rated dynamic current (peak) | kA | 63/80 | 63 | 80 |
Thermal current(4s) | kA | 25/31.5 | 25 | 31.5 |
Rated short-circuit making current(peak) | kA | 63/80 | 63 | 80 |
Rated operating sequence | 〇—0.3s—CO— 180s—00 | |||
Power frequency withstand voltage(1min) | kV | 95 | ||
Rated lightning impulse withstand voltage(peak) | 185 | |||
Mechanical endurance | Times | 10000 |